Descripción
Table of Contents
SH202L-C32
SH202L-C32
Technical
- Standards:
- IEC/EN 60898-1
- Product Name:
- Miniature Circuit Breaker
- Tripping Characteristic:
- C
- Rated Voltage (Ur):
- 400 V AC
- Rated Operational Voltage:
- acc. to IEC 60898-1 400 V AC
- Operational Voltage:
- Maximum (Incl. Tolerance) 440 V AC
Minimum 12 V AC
- Rated Insulation Voltage (Ui):
- acc. to IEC/EN 60664-1 440 V
- Rated Impulse Withstand Voltage (Uimp):
- 4 kV
at 2000 m 5 kV
at Sea Level 6.2 kV
- Dielectric Test Voltage:
- 50/60 Hz, 1 min: 2 kV
- Input Voltage Type:
- AC
- Rated Current (In):
- 32 A
- Rated Short-Circuit Capacity (Icn):
- (400 V AC) 4.5 kA
- Rated Conditional Short-Circuit Current (Inc):
- (400 V) 5 kA
- Rated Frequency (f):
- 50 / 60 Hz
- Power Loss:
- 7.4 W
at Rated Operating Conditions per Pole 3.7 W
- Power Supply Connection:
- Arbitrary
- Contact Position Indication:
- ON / OFF
- Energy Limiting Class:
- 3
- Electrical Endurance:
- 10000 AC cycle
- Mechanical Endurance (Nendu):
- 20000 cycle
- Number of Poles:
- 2
- Number of Protected Poles:
- 2
- Overvoltage Category:
- III
- Product Range:
- SH200L
- Tightening Torque:
- 2 N·m
- Actuator Type:
- Toggle
- Screw Terminal Type:
- Cage Terminal
- Actuator Marking:
- I / O
- Actuator Material:
- Insulation Group II, Black, Sealable
- Housing Material:
- Insulation Group II, RAL 7035
- Mounting on DIN Rail:
- TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
- Mounting Position:
- Any
- Recommended Screw Driver:
- Pozidriv 2
- Accessories Available:
- No
- Connecting Capacity:
- Conductor 25 / 25 mm²
Flexible with Ferrule 0.75 … 16 mm²
Flexible 0.75 … 16 mm²
Rigid 0.75 … 25 mm²
Stranded 0.75 … 25 mm²
- Installation Size:
- acc. to DIN 43880 1
- Terminal Type:
- Screw Terminals
Environmental
- Ambient Air Temperature:
- Operation -25 … +55 °C
Storage -40 … +70 °C
- Reference Ambient Air Temperature:
- 30 °C
- Degree of Protection:
- IP20
Enclosure with Cover IP40
- Pollution Degree:
- 2
- Environmental Conditions:
- 28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
- Resistance to Vibrations acc. to IEC 60068-2-6:
- 5g, 20 cycles at 5 … 150 … 5 Hz with load 0.8 In
- Resistance to Shock acc. to IEC 60068-2-27:
- 25g / 2 shocks / 13 ms
- RoHS Status:
- Following EU Directive 2011/65/EU
- Environmental Information:
- 2CDK400030D0201
Dimensions
- Width in Number of Modular Spacings:
- 2
- Product Net Width:
- 35 mm
- Product Net Height:
- 88 mm
- Product Net Depth / Length:
- 69 mm
- Product Net Weight:
- 0.25 kg
- Pole Net Weight:
- 0.115 kg
- Built-In Depth (t2):
- 69 mm
Container Information
- Package Level 1 Units:
- carton 5 piece
- Package Level 1 Width:
- 92 mm
- Package Level 1 Height:
- 80 mm
- Package Level 1 Depth / Length:
- 183 mm
- Package Level 1 Gross Weight:
- 1.3 kg
- Package Level 2 Units:
- 60 piece
- Package Level 2 EAN:
- 4016779988759
Ordering
- Minimum Order Quantity:
- 1 piece
- Customs Tariff Number:
- 85362010
- Country of Origin:
- Germany (DE)
- Selling Unit of Measure:
- piece
Certificates and Declarations (Document Number)
- Certification Agency:
- EN
IEC
- Declaration of Conformity – CE:
- 9AKK107046A5460
- Environmental Information:
- 2CDK400030D0201
- Instructions and Manuals:
- No document needed
- RoHS Information:
- 2CDK400030D0201
Popular Downloads
- Data Sheet, Technical Information:
- 2CSC400030D0202
- Instructions and Manuals:
- No document needed
Classifications
- ETIM 6:
- EC000042 – Miniature circuit breaker (MCB)
- ETIM 7:
- EC000042 – Miniature circuit breaker (MCB)
- ETIM 8:
- EC000042 – Miniature circuit breaker (MCB)
- EPLAN Catalog Tree:
- Electrical engineering / Protection devices / General
- EPLAN Function Definition:
- Circuit breaker / Double circuit-breaker / Double circuit breaker 1_2_3_4
- WEEE Category:
- 5. Small Equipment (No External Dimension More Than 50 cm)
- WEEE B2C / B2B:
- Business To Consumer
- CN8:
- 8536 20 10
- UNSPSC:
- 39121614
- eClass:
- V11.0 : 27141901
- Object Classification Code:
- F
Valoraciones
No hay valoraciones aún.